Legionella pneumophila contamination in central air-conditioning systems of public places in China:a meta-analysis |
FANG Zisi1, LIAO Hui1, ZHOU Xiaocong1, XU Hong2
|
1. School of PublicHealth, Zhejiang University of Traditional Chinese Medicine, Hangzhou, Zhejiang 310053, China; 2. Hangzhou Center for Disease Control and Prevention, Hangzhou, Zhejiang 310021, China |
|
|
Abstract Objective To systematically evaluate the detection of Legionella pneumophila in central air-conditioning systems of public places in China, so as to provide insights into the management of L. pneumophila contamination. Methods The publications pertaining to L. pneumophila contamination in central air-conditioning systems of public places in China were searched in international and national databases, including CNKI, Wanfang Data, CBM, PubMed and Web of Science from January 1, 2010 to December 31, 2022. The publication quality was evaluated using the Strengthening the Reporting of Observational Studies in Epidemiology. A meta-analysis was performed using the software Stata version 16.0. The pooled detection of L. pneumophila and its 95%CI were estimated. The publication bias was evaluated using Begg's test, and sensitivity analysis was performed with the leave-one-out evaluation for assessment of the robustness of the outcomes. Results A total of 742 publications were initially searched, and 29 publications were finally included, all of which were cross-sectional studies. The publications included 10 high-quality and 19 moderate-quality studies covering 6 160 samples, and the pooled detection of L. pneumophila was 17.20% (95%CI: 12.80%-21.90%). Subgroup analysis showed a higher detection rate of L. pneumophila in cooling water (21.80%) than in condensed water (5.50%) (P<0.01). According to the criteria defined in Hygienic Specification of Central Air-conditioning Ventilation System in Public Buildings (2006 version), the detection of L. pneumophila was 23.30%, which was higher than the detection (13.20%) according to the Hygienic Specification of Central Air-conditioning Ventilation System in Public Buildings (WS 394-2012) (P<0.05). The detection of L. pneumophila did not vary in place, region or sample (P>0.05). Begg's test showed no significant publication bias, and sensitivity analysis showed robustness of the results. Conclusions The detection of L. pneumophila ranges from 12.80% to 21.90% in central air-conditioning systems of public places in China. Health and environmental protection sectors need to improve the monitoring of L. pneumophila contamination in central air-conditioning systems of public places.
|
Received: 24 February 2023
Revised: 05 April 2023
Published: 15 May 2023
|
|
|
|
|
[1] FIELDS B S,BENSON R F,BESSER R E.Legionella and legionnaires' disease:25 years of investigation[J].Clin Microbiol Rev,2002,15(3):506-526. [2] 张屹,贾予平,沈凡,等.公共建筑冷却塔军团菌污染水平与环境因素现况调查[J].首都公共卫生,2016,10(1):6-9. [3] BORGES V,NUNES A,SAMPAIO D A,et al.Legionella pneumophila strain associated with the first evidence of person-to-person transmission of legionnaires' disease:a unique mosaic genetic backbone[J/OL].Sci Rep,2016,6[2023-04-05] .https://doi.org/10.1038/srep26261. [4] 陈卫中,陈志健,何升良,等.浙江省公共场所集中空调通风系统卫生状况分析[J].预防医学,2019,31(10):1048-1050. [5] CUNHA B A,BURILLO A,BOUZA E.Legionnaires' disease[J].Lancet,2016,387(10016):376-385. [6] 刘慧,陈丽琼,卢彩兰,等.公共场所集中空调通风系统卫生状况研究进展[J].中国卫生工程学,2020,19(3):477-479. [7] VON ELM E,ALTMAN D G,EGGER M,et al.The strengthening the reporting of observational studies in epidemiology(STROBE)statement:guidelines for reporting observational studies[J].Int J Surg,2014,12(12):1495-1499. [8] 程慧,林奕芝,潘瑞胤,等.深圳市6家医院集中空调冷却水军团菌污染状况及其管理对策[J].职业与健康,2010,26(4):436-437. [9] 吴文斌,刘建忠,陈志平,等.泉州市公共场所集中空调通风系统卫生状况分析[J].医学动物防制,2011,27(2):134-136. [10] 钟嶷,杨轶戬,郭重山,等.广州市公共场所集中空调冷却水冷凝水军团菌污染调查[J].中国卫生检验杂志,2012,22(6):1418-1419,1425. [11] 冯锦姝,张志诚,余淑苑,等.深圳公共场所水系统嗜肺军团菌污染研究[J].中国卫生工程学,2012,11(1):32-33,36. [12] 吴浩生,林奕嘉,余伟欣,等.深圳市罗湖区医院、宾馆集中式空调系统卫生学评价[J].中国社会医学杂志,2012,29(3):219-221. [13] 刘月淑,王红娅,张桂芳,等.银川市酒店集中空调和洗澡热水军团菌污染分析[J].宁夏医学杂志,2012,34(1):65-67. [14] 江思力,石同幸,刘俊华,等.广州市办公大楼集中空调通风系统卫生状况分析[J].预防医学论坛,2014,20(4):250-252. [15] 张丽蓉,郭宝羡,姚海燕,等.漳州市2014年部分酒店/宾馆中央空调冷却塔/冷凝水嗜肺军团菌污染调查[J].海峡预防医学杂志,2015,21(5):62-63. [16] 林思仁,徐志华,叶思娟,等.惠州市公共场所集中空调通风系统卫生状况调查[J].环境卫生学杂志,2015,5(2):150-153. [17] 孙志峰,段旭,宋光辉.2014年北京市东城区公共场所集中空调通风系统污染状况分析[J].中国卫生检验杂志,2015,25(14):2401-2403. [18] 冯锦姝,余淑苑,张然,等.2012年10月—2013年10月深圳市公共场所水系统嗜肺军团菌污染现状[J].实用预防医学,2015,22(10):1235-1237. [19] 陈志永,陈小岳,秦黎霞.2011—2014年苏南某市公共场所集中空调水系统嗜肺军团菌污染状况分析[J].环境卫生学杂志,2015,5(6):565-567. [20] 林奕嘉. 深圳市罗湖区公共场所集中空调通风系统冷却水、冷凝水卫生状况分析[J].疾病监测与控制,2016,10(3):210-211. [21] 叶思娟,林思仁,徐志华,等.惠州市某区公共场所集中空调通风系统微生物污染状况调查[J].中国卫生工程学,2017,16(4):461-464. [22] 石艳,汪百鸣,吴昕.合肥市2014—2015年公共场所集中空调通风系统卫生状况评价[J].安徽预防医学杂志,2017,23(5):345-347. [23] 陶利,汪静.公共场所集中空调冷却水军团菌污染现状研究[J].中国卫生产业,2017,14(26):40-41. [24] 张海霞,张美云,孙晓冰,等.2015年北京市某区星级酒店集中空调系统卫生情况[J].职业与健康,2017,33(2):248-250. [25] 冯锦姝,余淑苑,周国宏,等.2015—2016年深圳市公共场所空调系统嗜肺军团菌的污染状况[J].公共卫生与预防医学,2017,28(3):78-80. [26] 张浩玲,何伦发,郭艳,等.2013年—2015年某市公共场所集中空调通风系统微生物污染状况调查[J].环境卫生学杂志,2017,7(1):19-23. [27] 陈卫中,陈志健,何升良,等.浙江省公共场所集中空调通风系统污染监测结果分析[J].预防医学,2018,30(4):402-404. [28] 曾雪娇,杜喜浩,张佳,等.上海市轨道交通地下车站集中空调通风系统的卫生状况[J].环境与职业医学,2018,35(4):286-290. [29] 万枫,豆媛媛,田锋.2014—2017年新疆乌鲁木齐市妇幼保健医院中央空调系统军团菌检测结果[J].职业与健康,2018,34(17):2392-2394,2398. [30] 李婵媛. 2012年—2016年铁岭市公共场所集中空调冷却水、冷凝水嗜肺军团菌检测结果分析[J].中国卫生检验杂志,2018,28(1):120-121,123. [31] 史蓉婕,王希丹,龙冬玲,等.2014—2018年深圳市罗湖区公共场所集中空调通风系统卫生状况分析[J].环境卫生学杂志,2019,9(4):353-357. [32] 张海霞,张美云,孙晓冰,等.2018年北京市朝阳区二、三级医院集中空调系统卫生情况[J].职业与健康,2019,35(17):2397-2400. [33] 陈卫中,陈志健,何升良,等.浙江省公共场所集中空调通风系统卫生状况分析[J].预防医学,2019,31(10):1048-1050. [34] 龚华,钱春燕,全旭芳,等.2014—2018年上海市普陀区公共场所集中空调通风系统卫生状况调查[J].上海预防医学,2020,32(4):299-302,308. [35] 姜颖,范志伟,陈振发,等.2016—2019年深圳市南山区公共场所集中空调通风系统卫生状况调查[J].公共卫生与预防医学,2020,31(2):46-49. [36] 曾立爱,姜茗,刘成伟,等.江西省公共场所集中空调通风系统微生物污染状况调查[J].中国消毒学杂志,2022,39(3):183-185. [37] 金鑫,韩旭,耿莉,等.2006—2012年我国公共场所集中空调通风系统嗜肺军团菌污染状况Meta分析[J].环境与健康杂志,2015,32(3):225-230. [38] 章燕,冯智田,窦志勇,等.公共场所集中空调通风系统微生物污染现状[J].中国卫生监督杂志,2020,27(2):131-135. [39] 姜帅,余淑苑,陈国敏,等.《公共场所集中空调通风系统卫生规范》实施情况调查[J].环境卫生学杂志,2021,11(6):529-536. [40] 单聪. 空调冷却塔水嗜肺军团菌污染调查及其生物传感器快速检测方法的研究[D].北京:中国疾病预防控制中心,2010. [41] LIN H,XU B,CHEN Y,et al.Legionella pollution in cooling tower water of air-conditioning systems in Shanghai,China[J].J Appl Microbiol,2009,106(2):606-612. [42] AMEMURA-MAEKAWA J,KURA F,CHIDA K,et al.Legionella pneumophila and other Legionella species isolated from legionellosis patients in Japan between2008 and 2016[J/OL].Appl Environ Microbiol,2018,84(18)[2023-04-05] .https://doi.org/10.1128/AEM.00721-18. |
|
|
|