Hygienic status of central air conditioning ventilation systemsin public places in urban areas of Ma'anshan City |
LI Yanyan1,2, WEI Hao2, ZHOU Yan2, WANG Li2, YE Mengjuan2, SUN Yuanting2, GAN Junying2, BIAN Qian1,3
|
1. School of Public Health, Nanjing Medical University, Nanjing, Jiangsu 210000, China; 2. Ma'anshan Center for Disease Control and Prevention, Ma'anshan, Anhui 243000, China; 3. Jiangsu Center for Disease Control and Prevention, Nanjing, Jiangsu 210000, China |
|
|
Abstract Objective To investigate the hygienic status of the central air conditioner ventilation system in public places in urban areas of Ma'anshan City, Anhui Province, so as to provide insights into formulation of supervision and management interventions. Methods A total of 15 public places with the central air conditioner ventilation system were randomly sampled from main urban areas in Ma'anshan City in 2022. Sampling and detection were performed following the standard GB/T 18204.5—2013 Examination methods for public places Part 5: Central air conditioning ventilation system, including total number of bacteria and total number of fungus on the inner surface of wind pipes, total number of bacteria and fungus, particulate matter (PM10) and β-hemolytic streptococci in the air supply system, and Legionella pneumophila in the cooling water, and the detection indicators were assessed following the WS 394—2012 Guideline for hygiene of the central air conditioner ventilation system in public places. The eligible rate of samples, the detection rate of L. pneumophila were analyzed. Results A total of 368 samples were collected from 15 public places, and the qualified rate was 50.54%, no places had all eligible measurement indicators. The qualified rates of total bacteria and fungus numbers on the inner surface of wind pipes were 52.67% and 59.33%. The qualified rates of total bacterium number, total fungus number, PM10 and β-hemolytic streptococci were 12.00%, 28.00%, 90.00% and 96.00% in the air supply system. The qualified rates of samples in administrative workplaces, hotels, bathing places and malls (supermarkets) were 32.50%, 59.24%, 61.09% and 68.92%, the qualified rates of total bacteria on the inner surface of air ducts were 8.33%, 72.46%, 66.67% and 61.90%, and the qualified rates of total fungus numbers in air supply were 0, 21.70%, 33.30% and 71.40%, respectively, with statistical significance (P<0.05). A total of 18 cooling water samples were collected, and L. pneumophila was detected in three samples (16.67%). Conclusions Poor hygiene is seen in the central air conditioning ventilation systems in public places in main urban areas of Ma'anshan City. High attention needs to be paid to contamination of bacterium, fungus and L. pneumophila, and expansion of supervision coverage and improved supervision intensity are recommended.
|
Received: 11 September 2023
Revised: 30 October 2023
Published: 12 January 2024
|
|
|
|
|
[1] 陈卫中,陈志健,何升良,等.浙江省公共场所集中空调通风系统污染监测结果分析[J].预防医学,2018,30(4):402-404. [2] 徐珊珊,刘卫艳,吕烨,等.杭州市旅店业集中空调通风系统新风量调查[J].预防医学,2018,30(7):735-736. [3] 陈雪华. 室内空气主要污染物及其健康效应[J].中国卫生工程学,2014,13(2):170-171,173. [4] 中华人民共和国卫生部.公共场所集中空调通风系统卫生规范:WS 394—2012[S].2012. [5] 中华人民共和国国家质量监督检验检疫总局,中国国家标准化管理委员会.公共场所卫生检验方法第5部分:集中空调通风系统:GB/T 18204.5—2013[S].2013. [6] 袁丹茅,金建潮,钟叶平,等.龙岩市城区公共场所集中空调通风系统微生物污染状况调查[J].中国卫生工程学,2022,21(5):742-743,747. [7] 陈卫中,陈志健,何升良,等.浙江省公共场所集中空调通风系统卫生状况分析[J].预防医学,2019,31(10):1048-1050. [8] 黄意府,麻晓莉,王孔前,等.公共场所集中空调通风系统清洗消毒效果调查分析[J].应用预防医学,2020,26(3):247-248,251. [9] 佟冬青,陈加档,陈晟,等.2017—2018年温州市公共场所集中空调卫生状况调查[J].黑龙江医学,2019,43(12):1497-1499,1501. [10] 席映辉,席明毅,许友苓,等.2018年河北省廊坊市公共场所集中空调通风系统卫生状况调查[J].职业与健康,2019,35(9):1260-1262. [11] 陈健,刘洋,夏清云,等.马鞍山市公共场所中央空调军团菌污染状况[J].中华预防医学杂志,2006,40(2):104. [12] 方子思,廖辉,周筱丛,等.我国公共场所集中空调通风系统嗜肺军团菌污染的Meta分析[J].预防医学,2023,35(5):425-430. [13] 耿志,孙露.合肥市22家公共场所集中空调通风系统卫生状况[J].安徽预防医学杂志,2022,28(3):212-214,233. [14] 刘晓曦,张之幸,戴俊明,等.2020年上海市长宁区44家公共场所集中空调通风系统卫生状况分析[J].中国卫生监督杂志,2022,29(1):62-67. [15] 邱玉蓉,胡燕.2020年成都市青羊区42家集中空调通风系统卫生状况调查报告[J].口岸卫生控制,2022,27(2):55-58. |
|
|
|